ATEX Zones 1 & 2
A range of Switch Disconnectors housed in heavy duty cast enclosures - ATEX certified for use in Cat II, Zones 1&2 environments.
Certifications and Approvals
• Certification Code Ex d II 2 GD IIB T4, T5 or T6 (Contents dependent)
• Certification No. ITS 09 ATEX 16433X, ITS 09 ATEX 16436U
• Certification standard EN 60079-0, EN 60079-1, EN 61241-0 & EN 61241-1
• Operating temperature -20oC to +40oC
• Ingress Protection IP65
Construction

High quality heavy duty cast enclosures are used throughout the range. (Cast Iron 16A - 80A, Cast Aluminium 63A - 250A)
All enclosures are supplied pre-drilled with the entries as shown against each item. Entries can be fitted with reducers to suit smaller cables, but specific entry arrangements can be supplied. Please contact our technical sales staff to discuss your specific requirements.
All load switching interiors are supplied as either TP&N (switched neutral) or 6P and have AC23A ratings to BS EN 60947-3.
Auxiliary contacts are available for applications such as SCADA packages.
Operating handles are capable of accepting up to three padlocks in the 'Off' position.
Finish - RAL 7035 Two pack grey epoxy coating over etching primer.
Technical data sheet for this range.